Tertiary winding working and application
In this article we will discussed about Tertiary
winding working and application and also their uses.
There are many reasons for which three winding transformer
is employed . Some of the reasons are listed below.
1. If a two winding transformer has to supply an additional
load which has to be insulated from the secondary windings for some reasons the
three winding transformer may be used with additional load carried by tertiary winding.
2. The phase compensating devices can be supplied with three
winding transformer which are not operating at either primary or secondary
voltage but at some different voltage.
3. The tertiary winding can be used as a voltage coil in a
testing transformer.
4. Three supply systems operating at different voltages can
be interconnected using three winding transformer.
5. The three winding transformer can be used to load large
split winding generators.
6. The substations requirements can be met using three
winding transformer which requires a voltage different from that of primary and
secondary windings.
7. The tertiary winding connected in delta reduces the
impedance offered to the zero sequence currents so that a larger earth fault
current flows for proper operation of protective equipment. For unbalanced load
it limits the imbalance in voltage. It permits the flow of third harmonic
current to reduce harmonic voltage.
Stabilization Due to tertiary winding
For unbalanced single phase load, the star-star connection
offers high reactance to the flow of current. Any unbalanced load current has
three components viZ. Positive and zero sequence components.
The zero sequence component on the secondary side cannot be
balanced by primary currents as zero
sequence currents cannot flow in the isolated neutral of star connected
primary. On the secondary side the zero sequence current sets up magnetic flix
in the core. The iron path is available for this flux and the impedance offered
to the flow of zero sequence current is lowered. For this purpose the tertiary
winding is called stabilizing winding.
Suppression of triple frequency currents by tertiary winding
In the figer the generator neutral is connected to the
neutral of the primary of transformer. The neutral of the load in connected to
the neutral of the secondary o the transformer. If there is a third harmonic in
the wave form of the generator phase voltage, this third harmonic will appear
on the secondary phase voltage and the triple frequency secondary current will
flow. In the neutral wire, all the triple frequency currents for the three
phases will be added and flow.
![Tertiary winding working and application , reason of use of tertiary winding Tertiary winding working and application , reason of use of tertiary winding](https://blogger.googleusercontent.com/img/b/R29vZ2xl/AVvXsEh25_O5BFqUp-Go1pmyqSHn_WCTIZC_rDmP5NftiKj1apb6OX_rSVcT5mEwnGnvVrhO6sTwwsVpiHQmuL_itpOZWssUUENamQWIklP1CMwc6fV-sPW8EuJbp9LREGk4x-ZuPbRTYNgJ1yA/s1600/7-three-phase-transformers-24-638.jpg)
These currents will interfere with the neighboring telephone
circuits. if the primary natural condition is not made , then there will be
no return path for the triple frequency component
of exciting current. In that case, third harmonic will appear on each phase
voltage of the transformer, distorting the flux in the transformer. Now, if the
secondary neutral is connected, then the triple frequency harmony currents will
be developed in the secondary circuits. These currents will also interfere with
telecommunication lines. If both the neutrals of primary and secondary are
insulated, there will ve triple harmonics
in the voltage wave of each phase of the transformer .
On the other hand, if the neutral points are not insulated,
the voltage regulation of the several phases will be poor if the load is
unbalanced which is the usual case with the practical loads.
Now,it is required to suppress the tiple frequency secondary currents. This can be done by providing a delta-connected
transformer. The tertiary winding
are
connected in delta. The EMF which will be doweled in the tertiary delta due to
fundamental frequency will be balanced,. The induced EMF of triple frequency will ve in time phase
around the closed circuit. The KVA rating of the tertiary winding will be a
very small fraction of that of the main transformer. Only due to possible
short-circuit conditions, the tertiary is generally designed to have a rating
about one-third of the rating of the main winding.